Sl.No Item Name Quantity
1 AIR CONDITIONING PLANTS - Dismantling of existing plant including 2 Nos reciprocating compressor and motor, 2 nos cooling tower, 1 Nos fresh air blower, 1 Nos cement plastered AHU, 2 Nos blowers etc. Details are as per Annexure-I. 1Lot
2 AIR CONDITIONING PLANTS - Supply of factory assembled, Air - cooled, scroll chiller packages of minimum capacity of 40 TR (120000 Kcal/hr). Technical details are as per Annexure-II. 1Each
3 AIR CONDITIONING PLANTS - Supply of suitable model pump set of horizontal split case pump. The pump shall handle minimum 365 lpm of water against head of minimum 25M. Details are as per Annexure-III. 2Each
4 AIR CONDITIONING PLANTS - Supply of dia 100 MS C class pipe with insulations. Details are as per Annexure - IV. 100m
5 AIR CONDITIONING PLANTS - Supply of dia 50 mm MS C Class pipe with insulation (Drain pipe). Details are as per Annexure-IV. 30m
6 AIR CONDITIONING PLANTS - Supply of dia 32 MS C class pipe with insulation (Expansion tank pipe). Details are as per Annexure-IV. 35m
7 AIR CONDITIONING PLANTS - Supply of Dia 100 mm butterfly valve. Details are as per Annexure-IV. 8Each
8 AIR CONDITIONING PLANTS - Supply of Dia 100 mm Motorized butterfly valve. Details are as per Annexure-IV. 8Each
9 AIR CONDITIONING PLANTS - Supply of 100 mm dia manual balancing cum flow measurement valve (Advance make or equivalent). Details are as per Annexure-IV. 2Each
10 AIR CONDITIONING PLANTS - Supply of 100 mm dia flexible pipe connector. Details are as per Annexure-IV. 8Each
11 AIR CONDITIONING PLANTS - Supply of 100 mm dia Y strainer. Details are as per Annexure-IV. 2Each
12 AIR CONDITIONING PLANTS - Supply of 100 mm dia non return valve. Details are as per Annexure-IV. 3Each
13 AIR CONDITIONING PLANTS - Supply of 80 mm dia 3 way modulating valve with motor and thermostat. Details are as per Annexure-IV. 1Each
14 AIR CONDITIONING PLANTS - Supply of 80 mm dia globe valve. Details are as per Annexure-IV. 1Each
15 AIR CONDITIONING PLANTS - Supply of 100mm dia pressure guage (with pet cock/gate valve). Details are as per Annexure-IV. 8Each
16 AIR CONDITIONING PLANTS - Supply of differential pressure switch. Details are as per Annexure-IV. 1Each
17 AIR CONDITIONING PLANTS - Supply of dial type temperature guage. Details are as per Annexure-IV. 8Each
18 AIR CONDITIONING PLANTS - Supply of Automatic air Vent. Details are as per Annexure-IV. 6Each
19 AIR CONDITIONING PLANTS - Supply of drain plug. Details are as per Annexure-IV. 6Each
20 AIR CONDITIONING PLANTS - Supply of suitable GRP panel expansion tank as per attached specification of size 0.75 m x 1.0 m x 1.0m (0.75 cubic metre capacity) insulated with 40 mm thick polyurethane foam. Details are as per Annexure - I. 1Each
21 AIR CONDITIONING PLANTS - Supply of Automation for AC plants as per Annexure - I. 1Lot
22 AIR CONDITIONING PLANTS - Supply of electrical panel catering to 1 nos Aircooled scroll chiller packages and 2 nos Chilled water Pumps as per Annexure - V. 1Sets
23 AIR CONDITIONING PLANTS - Supply of double skin 34000 CMH clean room AHU with 100 mmwc static pressure and standby motor as per Annexure-VI. 1Each
24 AIR CONDITIONING PLANTS - Supply of Fresh air double skin AHU without cooling coil 4420 CMH, 100 mmwc static pressure as per Annexure VI. 1Each
25 AIR CONDITIONING PLANTS - Supply of Five micron filters for prefiltration of air down to 5 microns at an efficiency of 98.5% plus. Each filters shall be as size as 610 x 610 x 150 mm and as per Annexure - I. 20Each
26 AIR CONDITIONING PLANTS - Supply of HEPA filters of minimum size 610 x 610 x 300 mm (inclusive of 6 mm gasket on both side) to filter 1700 cmh of air to 0.3 micron as per Annexure - I. 20Each
27 AIR CONDITIONING PLANTS - Supply of aluminium ducting (site fabricated / prefabricated) for supply and return air of 1 mm thickness as per Annexure - VII. 125m2
28 AIR CONDITIONING PLANTS - Supply of aluminium ducting (site fabricated/prefabricated) for supply and return air of 1.8 mm thickness as per Annexure - VII. 25m2
29 AIR CONDITIONING PLANTS - Supply of nitrile rubber (closed cell) thermal insulation for supply and return air duct with minimum 19 mm thick as per Annexure - I. 160m2
30 AIR CONDITIONING PLANTS - Supply of volume control dampers in supply air duct made of extruded alluminium complete with linkage, lever, fixing arrangement etc compatible for clean room standards. 10m2
31 AIR CONDITIONING PLANTS - Supply fresh air louver made of extruded alluminium with bird/insect screen provided with intake louver. 4m2
32 AIR CONDITIONING PLANTS - Supply of duct silencer to be provided in SA and RA duct. The silencer shall be designed to attenuate noise to meet NC-50 curve in cleanrooms. 6m2
33 AIR CONDITIONING PLANTS - Supply of factory fabricated motorized fire & smoke dampers with the actuators in supply and return air path as per Annexxure - I. 6m2
34 AIR CONDITIONING PLANTS - Supply of heating kit. The minimum capacity of heating kit shall be 33 Kw. The heating kit shall be as per Annexure-I. 1Sets
35 AIR CONDITIONING PLANTS - Stainless steel pan humidifier kit of minimum 9 Kw capacity for seasonal operation as per Annexure - I. 1Each
36 AIR CONDITIONING PLANTS - Supply of VFD of 20 Kw capacity for clean room AHU fan speed control as per Annexure - I. 1Each
37 AIR CONDITIONING PLANTS - Supply of electrical panel catering to Cleanroom AHU and FA AHU etc as per Annexure-V. 1Sets
38 AIR CONDITIONING PLANTS - Civil work comprising of pedestal for 1 nos of chiller, 2 Nos of pumps and 1 Nos of cleanroom AHU and 1 Nos of Fresh air AHU as per Annexure-I. 1Lot
39 AIR CONDITIONING PLANTS - Painting of all above mentioned equipments as per Annexure - I 1Lot
40 AIR CONDITIONING PLANTS - Installation, testing, balancing and commissioning of all the equipments mentioned above and validation of 1,00,000 class cleanroom as per Annexure - I. 1Lot