Sl.No Item Name Quantity
1 XLPE INSULATED 1.1 KV GRADE ALUMINUM CONDUCTOR CABLES : Supply of 3.5 Core X 240 sqmm, armoured , XLPE insulated, Aluminium conductor UG cable as per sl no. 1 of Table-1 and Annexure-1A and Annexure -A, B, C. 2,600m
2 XLPE INSULATED 1.1 KV GRADE ALUMINUM CONDUCTOR CABLES :Supply of 3.5 Core X 185 sqmm, armoured , XLPE insulated, Aluminium conductor UG cable as per sl no. 2 of Table-1 and Annexure-1A and Annexure- A,B,C. 600m
3 Laying of UG Cable: Laying of three runs of 240 sqmm cable in ground with protection bricks etc as per sl no.3 of Table-I and Annexure-1B 50m
4 Laying of UG Cable : Laying of one / two runs of 185 sqmm cable in existing trench as per sl no.4 of Table-I and Annexure-1C 350m
5 Laying of UG Cable : Laying of three runs of 240 sqmm cable in existing trench as per sl no.5 of Table-I and Annexure-1C 810m
6 Cable Termination : Termination of 3.5 Core X 185 and 240 sqmm UG cable as per sl no.6 of Table-I and Annexure 1(D) 66Nos.
7 ELECTRICAL PANELS: Supply of Three phase , 415V , 50Hz rated power control centre / panel as per sl no.7 of Table-I and Annexure 2(A) & BOM 2(A) and Annexure -A,B,C,D 1Sets
8 ELECTRICAL PANELS: Supply of Three phase , 415V , 50Hz rated power control centre/panel as per sl no.8 of Table-I and Annexure 2(A) & BOM 2(A1) and Annexure -A,B,C,D 1Sets
9 ELECTRICAL PANELS: Supply of Three phase , 415V , 50Hz rated power control centre/panel as per sl no.9 of Table-I and Annexure 2(A) & BOM 2(A2) and Annexure -A,B,C,D 1Sets
10 Installation , testing and Commissioning of PCC Panel 1 :Installation and commissioning of power control centre (at sl no. 7, 8 & 9 above) as per sl no.10 of Table-I 3Sets
11 Installation , testing and Commissioning of PCC Panel 2 : Installation and commissioning of Automatic Voltage Regulator, 400kVA, 415 V , 50Hz rated as per sl no.11 of Table-1 2Sets
12 Cable Termination: Termination of all the outgoing cables (Copper/Aluminium) 50 to 95 sqmm (with up to 3/4/5 cores) as per sl no. 12 of Table-I and Annexure-1(D) 120Nos.
13 ELECTRICAL CABLES : Supply of single core x 95sqmm copper cable as per sl no.13 of Table-I and Annexure3 (A) and Annexures A,B,C. 2,000m
14 CABLE LAYING: Laying of single core two rum per phase x 95 sqmm cable on wire mesh cable tray / in existing trench/ hume pipe as per sl no. 14 of Table -I and Annexure-1(C) 2,000m
15 ELECTRICAL PANELS: Supply of three phase, 415V, 50Hz UPS Output Panel as per sl no.15 of Table-I and Annexure 4(A) and BOM 2 (A3) and Annexure -A,B,C,D 2Sets
16 Installation , testing and Commissioning of PCC Panel 3: Installation and commissioning of the above panel as per sl no.16 of Table-I . 2Sets
17 Change over Panels: Supply of Change over panel as per sl no.17 of Table-I and Annexure-5(A), BOM 2(A4) and Annexure -A,B,C,D. 1Sets
18 Installation , testing and Commissioning of PCC Panel 3 :Installation and commissioning of the above mentioned changeover panel as per sl no.18 of Table-I 1Sets
19 ELECTRICAL CABLES: supply of 4CX 95sqmm copper conductor PVC insulated and PVC sheathed cable as per sl no.19 of Table-I and Annexure 6(A) and Annexures A,B , C 1,100m
20 CABLE LAYING: Laying of above cable (4CX95sqmm) in existing trench/ hume pipe/cable tray /on the wall as per sl no.20 of Table -I and Annexure 1(C) 800m
21 Cable Termination: Termination of above cable (4CoreX50/ 95sqmm cable) as per sl no.21 of Table-I and annexure 1(D) 60Nos.
22 ELECTRICAL PANELS: Supply of three phase output panel for STS as per sl no. 22 of Table-I and Annexure-7 (A) & BOM 2 (A5) and Annexures A,B C,D. 4Sets
23 Installation , testing and Commissioning of PCC Panel 1 : Installation of STS Output Panel as per sl no.23 of Table-1 4Sets
24 ELECTRICAL PANELS: Supply of UPS Distribution Panel as per sl no. 24 of Table-1 and Annexure 8(A) and BOM with same Annexure 8(A) 8Sets
25 Installation , testing and Commissioning of PCC Panel 1: Installation and commissioning of above UPS panel (supplied in sl no.24) as per sl no.25 of Table-1 8Sets
26 ELECTRICAL CABLES: Supply of 4CoreX50sqmm copper conductor PVC insulated cable as per sl no.26 of Table-1 and Annexure-6(A) and Annexures A, B, C 700m
27 ELECTRICAL CABLES: Supply of 5 Core X16 sqmm copper conductor PVC insulated cable as per sl no.27 of Table-1 and annexure-6(A) and Annexures A,B , C 800m
28 ELECTRICAL CABLES: Supply of 4CoreX4sqmm copper conductor PVC insulated cable as per sl no.28 of Table-1 and Annexure-6(A) and Annexures A,B , C 1,600m
29 ELECTRICAL CABLES: Supply of 5CoreX10sqmm copper conductor PVC insulated cable as per sl no.29 of Table-1 and Annexure-6(A) and Annexures A,B , C 2,400m
30 ELECTRICAL CABLES: Supply of 3CoreX4sqmm copper conductor PVC insulated cable as per sl no.30 of Table-1 and Annexure-6(A) and Annexures A,B , C 3,000m
31 ELECTRICAL CABLES: Supply of 3CoreX2.5sqmm copper conductor PVC insulated cable as per sl no.31 of Table-1 and aAnnexure-6(A) and Annexures A,B , C 2,250m
32 ELECTRICAL CABLES: Supply of 3 Core X1.5 sqmm copper conductor PVC insulated cable as per sl no.32 of Table-1 and Annexure-6(A) and Anexures A,B , C 1,000m
33 CABLE LAYING: Laying of above cables (sl no.26 to 32) in existing trench/hume pipe /tray as per sl no. 33 of Table-1 and Annexure-1C and Annexures-A,B and C 11,750m
34 Cable terminations: Termination of the above cable (3C/4C/5CX 1.5 to 16 sqmm) as per sl no.34 of Table-1 and Annexure-1(D) and Annexures- A, B and C 300Nos.
35 Soft Starters: Supply of soft starter with enclosure as per sl no. 35 of Table-1 and Annexures-A,B and C 8Sets
36 INSTALLATION CHARGES Installation and commissioning of soft starter(supplied in sl no.35) as per sl no. 36 of Table -1 8Sets
37 CABLE TRAY: Supply and fixing of steel wire mesh cable tray 150mm width X 50 to 54mm height as per sl no.37 and 37.1 and Annexures- 9(A), A,B and C 500m
38 CABLE TRAY: Supply and fixing of steel wire mesh cable tray 300mm width X 50 to 54mm height as per sl no.37 and 37.2 and Annexures-9 (A) , A,B and C 500m
39 Pipe Earthing: providing GI pipe earthing with 2.5 Mtr depth as per sl no. 38 of Table-1 and Annexures-A,B and C 8Sets
40 Earthing GI Strip / Flat: Supply and laying of GI earth strip 32X6mm as per sl no. 39 and 39.1 of Table-1 and Annexures-A,B and C 600m
41 Earthing copper strip: Supply and laying of copper earth strip 25X6mm as per sl no. 39 and 39.2 of Table-1 and Annexures-A,B and C 400m
42 GI WIRES: Supply and laying of GI earth wire 8SWG as per sl no. 39 and 39.3 of Table-I and Annexures-A,B and C 400m
43 DISTRIBUTION BOARDS (DBs): Supply , installation, Testing and commissioning of TPN distribution board as per sl no. 40 of Table-1 and Annexures-2 (A) common specifications for panels, Annexures- A,B and C 16Sets